- 153,800 sq ft building
- No advertising of SAVVIS name (plain wrapper)
- Interior and exterior security managed 24/7 by permanently
assigned staff of Wackenhut guard
|
- Biometric hand scanner requires ID card access and
hand geometry measurements
- Customer IDC access and contacts managed via Siebel
- Current government-issued picture ID required
- ID badge and biometric hand scan to man trap with
badge reader
- Second hand scans to gain access to raised floor
Biometric scanner captures 3D measurements of hand
|
- Multiple 360 degree cameras with 10x zoom
- More than 100 fixed cameras
- High speed recorders with DV cassette tapes
- Hard drives to eliminate down time for tape swaps
and over recording
- Minimum 30 day tape storage
|
- Backup power
- Multiple CAT Diesel 20 megawatt generators
- Minimum 24 hour fuel storage
- Agreements with two major carriers to provide additional
diesel fuel
- Generators assumes building load within 20 seconds
- Generators are tested on weekly basis under load
- Tanks are kept at least 80% full at all times
|
- Diverse paths to the building
- Feeds to building are encased in concrete
- Fed from two independent substations
- Separate transformers fed from both utility sources
for redundancy
|
- Hosting space HVAC system includes (16) AHUs and
(16) ACCUs manufactured by Trane
- AHUs are DX type and located in the mechanical mezzanine;
the ACCUs are located on the roof
- There is adequate capacity to withstand a HVAC unit
failure or an entire bus failure
- Cooling is provided by both overhead and under floor
air
- HVAC systems have wetted media for humidification,
VFDs for each supply fan, exhaust fans to control
building pressure, and economizers to utilize cool
outside air
- Separate Dectron outside air handling units provide
conditioned air for the hosting space
- UPS Room cooling is provided by Trane RTUs in a
N+1 configuration
- Node room cooling is provided by Liebert DX CRAC
units in a N+1 configuration
|
- Multiple fiber providers for diversity - provides
diversity and redundancy
- Each vendor can deliver additional bandwidth capacity
with minimal turn-around time
- Can be delivered using existing ‘lit’
fiber
- Fiber pathways into the Datacenter are truly diverse
- Fiber enters building in steel conduit from multiple
points in the building
|